Quality  |   Introduction  |   Solutions  |   Products  |  Resources  |   Technical Library  |   Links  |   Contact Us  |   Home
 

2SY212 Synchronising Check Relay

The 2SY212 synchronism check relay is designed to measure the phase angle between the monitored single phase voltages on the line & bus sides of a circuit breaker & verify that this angle is less than setting. If the measured angle has met this criteria for the time period defined by setting & the voltage magnitudes meet the criteria established by the Live Line/Bus & U/V Line/Bus settings, the output relay will be energised & the breaker permitted to close. Resetting will occur if either the phase angle or voltage magnitude stray outside the pre-set limits or if the sync check enable input is de-energised. Front panel LED's provide visual indication of relay status & sync check function. Bus or Line U/V, Differential Voltage and Frequency Slip Close block functionality together with flexible synchronism check bypass logic caters for a diverse range of applications.

The standard Micro MATRIX human machine interface (HMI) is combined with fully solid state measuring circuitry to provide high accuracy, simple set up & flexible operation. Self-monitoring is carried out by hardware & software watchdogs. High contact rating output relays are employed. A USB programming port is provided for ease of establishing relay settings using a PC. Front panel mounted LED's provide visual indication of relay status & sync check function.

CONTROL FEATURES

  • Synchronism Check (25)
  • Adjustable phase angle and time delay
  • Flexible Live and Dead Voltage configuration
  • Bus or Line U/V Close Block
  • Voltage Differential Close Block
  • Frequency Slip Close Block
  • Flexible Synchronism Check Bypass Logic
  • Manual Safe to Close Feature

     

    METERING

  • Line & Bus voltage display
  • Relative phase angle display
  • Line & Bus frequency display
  • Frequency slip display

     

    uMATRIX PLATFORM

  • Large LED back lit display panel
  • System status LED indicators
  • Simple menu setting procedure
  • 40-300V DC aux. supply
  • 40-275V AC aux. supply
  • 20-70V DC aux. Optional
  • Self diagnosis & fail alarm

     

    COMMUNICATION

  • USB PC link
  • Non platform specific PC programming software
  • Optical isolated RS485 network port
  • MODBUS RTU compatible network protocol
  •  

     

    For RMS Direct Sales & Product Support Click Here

    ©1998-2012 Relay Monitoring Systems Pty. Ltd.      ACN 052 484 483     ABN 76 052 484 483